Features
● Magnet-helix indicating mechanism ideal for low DP measurement
● A wide selection ofranges from OPa to 60Pa at up to 30KPa
● Accuracy 2% of FS
● Inertia-free, drift-free pointer indication
● Identical mounting dimensions to Model 2000 from Dwyer
● OEM solutions available
Specifications
| Service: | Air and non-combustible, compatible gases |
| Ranges: | See Range Selection Chart |
| Accuracy: | ±2% of full span at 21℃ (±3% on 2000-0.50IN, 2000/Z-0.5IN, 2000-10MM, 2000-100Pa, 2000-125Pa and ±4% on 2000-0.25IN, 2000-6MM, 2000-60Paranges) |
| Ambient Temperature: | -7~60℃ |
| Pressure Limit: | -68~100KPa |
| Overpressure: | Relief plug opens at approximately 25Psig (172KPa) |
| Process Connections: | 1/8"female NPT duplicate high and low pressure taps: one pair side and one pair back |
| Case and Bezel Material: | Die cast aluminum |
| Weight: | 460g |
| Dial Size: | 4"Diameter |
| Mounting Position: | Vertical |
| Standard Accessories: | Two 1/8" NPT plugs for duplicate pressure taps, two 1/8" pipe thread to rubber tubing adapter, and three flush mounting adapters with screws |
Differential pressure gauge Applications:
The Magnehelic differential pressure gauge is widely used in various industries for measuring low-pressure differences. Common applications include:
HVAC Systems: Monitoring air pressure in ducts, filters, and cleanrooms.
Industrial Processes: Measuring pressure drops across filters, pumps, and blowers.
Laboratories: Ensuring proper airflow in fume hoods and controlled environments.
Medical Facilities: Monitoring pressure in isolation rooms and operating theaters.
Environmental Monitoring: Measuring differential pressure in environmental chambers or wind tunnels.
Pharmaceuticals: Ensuring cleanroom compliance by monitoring air pressure differentials.